Automated current control system of electrolyzers type ÀÑÓÒÑÝ
Equipment complete includes the following: rectifiers Â-ÒÏÏÄ-6,25ê-900; saturable reactors;
control panels of unit; control cabinets of saturable reactors; control cabinet of electrolyzers type
current.
It is possible a separate equipment set
Technical characteristics
| Rectifier Â-ÒÏÏÄ-6,25ê-900-1: |
|
|
rated overload d. c., À |
6250 |
|
rated constant voltage, V |
900 |
|
overall dimensions, mm
|
1620õ1000õ1750 |
|
mass, kg, not over than |
1200 |
|
Saturable reactor: |
|
rated overload d. c., À |
6300 |
|
control depth of rectifying voltage, V |
50 |
|
overall dimensions, mm |
1626õ744õ1410 |
|
mass, kg, not over than |
2035 |
|
Control cabinets of saturable reactors (ØÓÄÍ): |
|
supplying voltage, alternative one, three-phase one, 50 Hz, V |
380 |
|
quantity of control current independent circuits |
2 |
|
maximum control current, À |
7 |
|
signal of distant current assignment, V |
10 |
|
current unbalance between rectifying unit blocks, %, not over than |
1 |
|
overall dimensions, mm |
600õ400õ1400 |
|
mass, kg, not over than |
140 |
Control cabinet of electrolyzers type current (ØÓÒÑ):
|
supplying voltage, alternative one, three-phase one, 50 Hz, V |
380 |
|
input analogue signals, V |
10 |
|
output analogue signals of units current assignment, V |
10 |
|
input and output discrete signals, V |
27 |
|
current stabilization static accuracy of type, %, not worse |
1 |
|
current average value deviations of type, averaged for 12 hours, %, not over than
(control is performed by am-hours measurement for 12 hours)
|
0,2 |
|
change range of current setting, relative element |
0,85-1,0 |
|
quantity of rectifier units, controlled ØÓÒÑ, pcs. |
11 |
|
overall dimensions |
1060õ820õ2000 |
|
mass, kg, not over than |
200 |
light signalling – light-emmiting diode current reverse connection signal of type - current transducer signal in the rectifier current circuit
of type.
Carried out functions:
local current assignment of type; distant current assignment of type (with
electroplating decoupling); current stabilization of type; current measurement of type on signal with
current transducer of type; state control of rectifier units; drive control ÐÏÍ (operation mode –
automatics switching on signal from ØÓÄÍ; manual switching ÐÏÍ of separate transformers;
group manual switching). ØÓÒÑ provides possibility of consumed power limiting on external
signal.
Control panel of unit (ÙÓÀ):
|
supplying circuits voltage of signalling and protection, constant, V |
220 |
|
supplying voltage ØÓÄÍ and ÐÏÍ, alternative, 50 Ãö, V |
220/380 |
|
overall dimensions, mm |
2200õ820õ2000 |
|
mass, kg, not over than |
400 |
Carried out functions:
oil switch control, control and indication of power transformer state,
parameters measurement of rectifier blocks; power transformer protection, rectifier blocks, ÐÏÍ; voltage
supplying 220/380 V with frequency 50 Hz of cooling circuits , ÐÏÍ, ØÓÄÍ.
Operation conditions:
|
Equipment must be operated indoors and in environment, no-containing current-conductive dust
and caustic vapours, corroding metals and isolation.
Concentration of no-current-conductive dust mg/ì3, not over
|
0,5 |
|
Ambient air temperature, °Ñ |
îò +1 äî +40 |
|
Height above sea level, m, not over than |
1000 |
|
Relative air humidity at temperature 25 °Ñ, %, not over than |
80 |
|
Tester voltage of power circuits, kV, in use |
5 |
|
Isolation resistance in cool state, MOhm, not less |
5 |
According to the consumer requirements, it is possible to manufacture and set equipment at
other powers with other parameters.
 |