Automated current control system of electrolyzers type ÀÑÓÒÑÝT
Equipment complete includes rectifiers Â-ÒÏÏ-6,3ê-1ê-01 and control current cabinet of type
electrolyzers. It is possible a separate equipment set
Technical characteristics
| Rectifier Â-ÒÏÏ-6,3ê-1ê-01: |
|
Supplying mains: rated voltage of power circuit supply |
690 |
|
rated voltage of supplying control circuit, V |
380 |
|
rated frequency of supplying mains, Hz |
50 |
|
phase number |
3 |
|
Output parameters: - rated output current, À |
6300 |
|
rated output voltage, V |
1000 |
|
control range of output current, À |
0-6300 |
|
overall dimensions, mm |
1640x1000x1800 |
|
mass, kg, not over |
1360 |
|
Control cabinet of electrolyzers type current (ØÓÒÑ): |
|
supplying voltage, alternative one, three-phase one, 50 Hz, V |
380 |
|
input analogue signals, V |
10 |
|
output analogue signals of units current assignment, V |
10 |
|
input and output discrete signals, V |
27 |
|
current stabilization static accuracy of type, %, not worse |
1 |
|
current average value deviations of type, averaged for 12 hours, %, not over than
(control is performed by am-hours measurement for 12 hours)
|
0,2 |
|
change range of current setting of type , kA |
0,85-1,0 |
|
quantity of rectifier units, controlled ØÓÒÑ, pcs. |
20 |
|
overall dimensions |
1060õ820õ2000 |
|
mass, kg, not over than |
200 |
|
light signalling – |
light-emmiting diode |
|
cable length of connection between ØÓÒÑ and rectifiers, m, not over than |
170 |
|
current reverse connection signal of type – signal from current meter of type “Halmer” |
1 kA/1 ìB |
Carried out functions:
local current generation of type; distant current generation of type (with
electroplating decoupling); current stabilization of type; current measurement of type on signal with
current transducer of type; state control of rectifier units; drive control ÐÏÍ (operation mode –
automatics switching on signal from rectifier; manual switching ÐÏÍ of separate transformers;
group manual switching).
Operation conditions:
Equipment must be operated indoors and in environment, no-containing current-conductive dust
and caustic vapours, corroding metals and isolation.
|
Concentration of no-current-conductive dust mg/ì3, not over |
3 |
|
Ambient air temperature, °Ñ |
îò +1 äî +40 |
|
Height above sea level, m, not over than |
1000 |
|
Relative air humidity at temperature 25 °Ñ, %, not over than |
80 |
|
Tester voltage of power circuits, kV, in use |
2,5 |
|
Isolation resistance in cool state, MOhm, not less |
5 |
According to the consumer requirements, it is possible to manufacture and set equipment at
other powers with other parameters.
 |